用最简单的表述解析术语---**Extraction Content:** **Title/Context:** 前計算例 (図 2-5-29) にさらに逆変換装置を用いた発電設備等を連系する場合の短絡容量計算は以下のように実施する。 **Diagram Description:** * **Type:** Single-line diagram of a power system. * **Main Elements:** * **Left side (System Interconnecter side):** * Source labeled "220kV". * Two parallel transformers, each labeled "300MVA, %Z=0.2% (100MVAベース)" and "300MVA, %Z=0.6% (100MVAベース)", connected from the 220kV source to a bus labeled "系統母線" (System bus). * **Middle Section:** * An interconnecting line labeled "連絡線, %Z=0.7% (1MVAベース)" connecting the "系統母線" to another bus labeled "短絡容量計算点 (L)" (Short-circuit capacity calculation point (L)). * **Right side (Recipient Equipment Installer side):** * The "短絡容量計算点 (L)" bus. * Four components connected to this bus via circuit breaker symbols: * An inverter device labeled "INV, 定格容量 10,000kW, 定格力率 100%". * An inverter device labeled "INV, 定格容量 8,000kW, 定格力率 100%". * A load labeled "L". * A load/generation unit labeled "L, 70,000kW (誘導電動機負荷換算)" and a generator labeled "G, 発電設備, %Z=1.8% (10MVAベース), 力率 0.9". These appear to be connected together before the breaker symbol. **Calculations and Explanations:** (1) 各逆変換装置を用いた発電設備等から発生する通電電流制限値 (容量) の合計を求めると、 10 × 1.5 + 8 × 1.5 = 27 (MVA) (2) 連系後の短絡電流 I_k は、図 2-5-29 で求めた短絡容量 P_s = 2,500 (MVA) を用いて P_s = 2,500 + 27 = 2,527 (MVA) I_k = (2,527 (MVA)) / (√3 × 66 (kV)) ≒ 22.1 (kA) となる。 なお、この短絡電流は無効電流であるため、短絡事故時における逆変換装置の設定力率への制御が十分に高速である場合、設定力率に応じた無効電流を短絡電流として計算することができる。 ※ 十分に高速であるとは、連系系統によって異なり、以下のようなケースがある。 ・ 短絡事故時に動作する保護装置等の動作時間よりも早い ・ 遮断器にトリップ指令が出るまでの時間よりも早い ・ 短絡電流に含まれる直流分及び逆変換装置からの無効電流により遮断器の定格短時間耐電流 (定格投入電流) を超過するおそれのある場合、短絡電流の最大波高値となる時間よりも早い **Figure Caption:** 図 2-5-31 逆変換装置を用いた発電設備等の短絡容量計算例